Reliable Power. Maximum Uptime.
Commercial
Generator Services
Complete generator solutions for your business. Installation, maintenance, repair, and 24/7 emergency service you can count on.
Get A Free Estimate
Scheduled Maintenance Plans
Annual Plan
(1) Full-Service Check: Performed by your Generac industrial factory authorized team.
Semi-Annual Plan
(1) Full-Service Check &
(1) Inspection Check: Performed by your Generac industrial factory authorized team.
Quarterly Plan
(1) Full-Service Check &
(3) Inspection Checks: Performed by your Generac industrial factory authorized team.
NFPA 110
Per Jurisdictional Code: Performed by your Generac industrial factory authorized team.
Standard Generator Scheduled Maintenance
SCOPE OF SERVICE CHECKS
Full-Service Check
- Replace engine lubricating oil and dispose of it environmentally responsibly.
- Replace oil filter(s) in natural gas engines.
- Replace oil and fuel filters in diesel engines and coolant filter if required.
- Inspect air filter(s) and crankcase breathers. Replace (additional cost) with client’s approval.
- Inspect the cooling system for leaks and conditions.
- Inspect and adjust belts as required.
- Natural gas/LPG fueled engines inspect spark plug wires and ignition system for damages and excessive wear.
- Inspect the generator fuel system for leaks or damage.
- Inspect wiring and connectors.
- Inspect battery(s) condition (load test) electrolyte levels, check for corrosion and battery charger function.
- Run the engine and check temperatures and pressures.
- Test the governor for proper operation and stability and inspect linkage.
- Test the engine safety shutdown systems.
- Test system for proper frequency/speed, voltage, and amperage.
- Inspect the transfer switch and perform the transfer with the client’s approval.
- Submit a written report to the client and advise of any further work required.
Inspection Check
- Inspect engine lubricating oil and coolant for proper levels and condition.
- Inspect air filter(s) and crankcase breathers. Replace (additional cost) with the client’s approval.
- Inspect the cooling system for leaks and conditions.
- Inspect and adjust belts as required.
- Natural gas/LPG fueled engines inspect spark plug wires and ignition system for damages and excessive wear.
- Inspect the generator fuel system for leaks or damage.
- Inspect wiring and connectors.
- Inspect battery(s) condition (load test) electrolyte levels, check for corrosion and battery charger function.
- Run the engine and check temperatures and pressures.
- Test the governor for proper operation and stability and inspect linkage.
- Test the engine safety shutdown systems.
- Test the system for proper frequency/speed, voltage and amperage.
- Inspect the transfer switch and perform the transfer with the client’s approval.
- Submit a written report and advise the client of any further work required.